Grout Testing: Cubes, Fluidity and Bleed

Choose grout tests for the job, read cube strength, flow and bleed results, and connect them to placement records.

Table of contents

Grout testing confirms that cement-based grouts placed on site have the strength, flow and stability the design relies on. In Australia it covers non-shrink grout under column baseplates and precast connections, post-tensioning duct grout, ground anchor and soil nail grout, and grout for masonry and other structural infill.

The core test is the grout cube compressive strength test. Cubes are made and cured to AS 1012.8.3 and crushed to AS 1012.9. Admixture-related grout testing references AS 1478.2, and NSW road and bridge work often specifies TfNSW TS 02800.49 (formerly RMS T375) for cubes made on site. Post-tensioning and ground anchor grouts add fluidity (efflux time) and bleed tests, usually to ASTM methods called up by state road authority specifications.

Grout performance can be affected by product selection, water content, mixing, placement, temperature and specimen handling. Good testing catches those problems while there is still time to act.


At a glance: grout strength, flow, bleed and placement records work together. Select tests for the application and product. Passing cubes do not prove that a connection or duct is fully filled.

Terms Explained

Term Plain-English meaning
Grout A material used to fill a gap, duct or connection. This article covers cement-based grout; epoxy and other resin grouts require their own specified methods.
Non-shrink grout A grout formulated to control volume change under stated test conditions. The name does not guarantee zero movement or a completely filled connection on site.
Fluidity and efflux time Fluidity describes flow behaviour. Efflux time is the seconds a defined quantity takes to leave a standard flow cone.
Bleed Water separating from fresh grout as solids settle. It can leave water pockets or voids.
Expansion An increase in grout volume. The measured result depends on when and how it is tested and whether expansion is restrained.
Annulus The ring-shaped gap around a bar, strand, pipe or anchor that grout is intended to fill.
Mud balance An instrument that measures fluid density using a known-volume cup and a balance arm.
Bond Transfer of force between grout and adjacent steel, concrete or ground. Cube compressive strength does not directly measure bond strength.

Choose Tests for the Grout Application

Application Main Concerns Typical Tests
Baseplate and bearing grout (columns, machinery, bridge bearings) Strength, full contact, no shrinkage gap Cube strength, flow
Precast connections (sleeves, dowels, panel joints) Strength, filling of ducts and sleeves Cube strength, flow
Post-tensioning duct grout Full encapsulation of strands, corrosion protection, no bleed voids Fluidity (efflux), bleed, cube strength, density
Ground anchors and soil nails Bond to strand/bar and ground, strength at stressing Fluidity, bleed, cube strength, density (w/c check)
Masonry core fill Strength, filling of cores Cube or cylinder strength depending on specification
Pile and void grouting Flow, strength Flow, cube strength

Before You Mix the First Bag

Confirm the approved product, application, water range, mixing equipment and time, placement temperature, working time and curing requirements. Working time is the usable period after mixing under the stated conditions; passing a flow test does not extend it.

Agree where samples will be taken. A sample at the mixer checks the mixed product; a sample at a duct vent can also show what has travelled through the system. Those records answer different questions and need distinct location labels.

Example: if a product’s approved instruction is 4.0 L of water per 20 kg bag, two bags need 8.0 L. The actual permitted range must come from that product’s approved instructions. Record measured water, product lot, grout temperature and mixing time so a low cube result can be investigated later.

Australian Standards and Specifications

Standard / Document Relevance
AS 1012.8.3 Making and curing mortar and grout cubes, in the laboratory or the field
AS 1012.9 Compressive strength of concrete, mortar and grout specimens
AS 1478.2 Sampling and testing admixtures for concrete, mortar and grout (grout cube appendix often referenced by manufacturers)
TfNSW TS 02800.49 (RMS T375) Grout cube compressive strength for cubes made on site (NSW)
TfNSW B113 / TS 00147 Post-tensioning of concrete and PT grout performance requirements
TfNSW, TMR, DTP and other ground anchor specifications Grout fluidity, bleed and strength for anchors
ASTM C939 Flow of grout by the flow cone (efflux time)
ASTM C940 Expansion and bleeding of grout
Manufacturer's technical data sheet Water content range, mixing time, curing, expected strengths

Grout Cube Compressive Strength Test

Cube Size

Cube Size Typical Use
50 mm Common for laboratory testing of fine grouts and mortars
70–75 mm Common for site-made cubes; many manufacturers and specifications use 75 mm

AS 1478.2 allows cube sizes from 50 to 75 mm, and RMS T375 / TS 02800.49 covers cubes in the same range. Use the cube size named in the specification and keep it consistent for the project.

Moulds

  • Use rigid steel or brass moulds with a cover plate
  • Plastic moulds or inserts are not suitable for grouts containing expansive additives, because the grout expands against a flexible mould and gives unrepresentative results
  • Coat moulds with release agent
  • Many non-shrink grouts are cured with the cover plate clamped down so the restrained expansion is reproduced

Making the Cubes

  1. Sample at the point of discharge (the pump outlet, the mixer or the duct vent), not from a bucket that has stood for an hour.
  2. Record the product, batch number, water added per bag, mixing time, grout and air temperature, and time of sampling.
  3. Fill the mould to a slight overfill. Tamp stiff or trowellable grouts to remove trapped air. Do not tamp flowable or fluid grouts.
  4. Screed the top flush with a sawing motion and clean the mould edges.
  5. Fit the cover plate and clamp it if the product is expansive.
  6. Label each cube and the sample record with the same identifier.

Curing and Transport

Use the mould restraint, initial curing, demoulding and transport conditions prescribed by the nominated method and product specification. Record temperature, moisture protection, timing and any departure. Do not assume a nominal 24-hour wait makes transport safe, particularly for cold conditions or early-age specimens. Distinguish standard-cured product/conformity specimens from specimens intended to represent site strength.

Testing

Cubes are crushed in compression in accordance with AS 1012.9. Load is applied on two cast faces, not the trowelled top face. The load is applied at the steady rate the method sets, which manufacturer guidance usually also refers to.

Cube strength (MPa) = maximum force (N) ÷ loaded area (mm²). Convert kN to N by multiplying by 1,000.

Under AS 1012.9, the loaded area comes from the measured dimensions across the loaded faces. TS 02800.49 / T375 instead use the nominal area unless the measured area differs from it by more than the method allows. Results are rounded as the method specifies.

Illustrative calculation: for a cube with a loaded area of 5,625 mm² under the selected method and a failure force of 225 kN, strength = 225,000 / 5,625 = 40.0 MPa. Use the method’s measured or nominal area rule; this arithmetic example is not an acceptance criterion.

Test Ages and Number of Cubes

Test Age Typical Purpose
1 day Early strength for stressing, de-propping or loading baseplates
3 days Early strength for ground anchors and PT works
7 days Strength development check
28 days Conformity with specified strength

The governing method and project specification set the number of cubes and test ages; there is no universal two-cubes-per-age rule. Write the required sample frequency, cube size, number at each age and reserve specimens into the inspection and test plan. Product comparison also requires the same specimen and curing method; a manufacturer’s laboratory value may not match a site-made cube result.

A grout cube result is not directly comparable with a concrete cylinder result. Cubes typically give higher values than cylinders for the same material.

Fluidity (Efflux Time) Test

For post-tensioning ducts and ground anchors, the grout must be fluid enough to fill the duct or annulus completely but not so wet that it bleeds and leaves voids.

The flow cone test (commonly ASTM C939) measures the efflux time: the time in seconds for a set volume of grout to flow out of a standard cone.

  • A longer efflux time indicates slower flow under the test conditions; it does not uniquely identify water–cement ratio. Product composition, mixing, temperature and elapsed time also matter
  • A shorter efflux time means a more fluid grout

Specifications typically set a target efflux time established in trials, with limits on how far site results may vary. Record the trial target, site limits and test temperature from the adopted anchor or PT specification; there is no single efflux-time limit for every grout. Fluidity is retested over time, because grout thickens as it ages in the mixer and may become hard to pump.

Bleed Test

Bleed water separates as solids settle and can leave voids in PT ducts. Specify the actual test configuration: ordinary bleeding/expansion testing to ASTM C940, a modified wick-induced test using strand, and pressure-bleed testing such as ASTM C1741 are different procedures. They are not interchangeable. Use the apparatus, duration, temperature and acceptance limit called up by the project’s adopted specification.

See the FHWA Post-Tensioning Tendon Installation and Grouting Manual for the distinction between bleed test configurations.

Density (Mud Balance)

Wet density, measured with a mud balance or specified known-volume container, is a useful consistency check against trial or product data. A lower value can indicate extra water, entrained air, a material change or a measurement problem; density alone does not uniquely determine water–cement ratio. For a known-volume check, divide the net grout mass by the calibrated container volume and report the units. Compare results only for the same product and approved procedure.

Typical Grout Test Frequencies

Test Typical Frequency
Fluidity At the start of grouting and at intervals during the day (e.g. one test every few hours, or per day)
Bleed Per day or per batch of material, per specification
Cube strength Per day, per batch of material or per quantity used
Density At the start and when water or material changes

Always use the frequency in the project specification. TfNSW B113, for example, sets its own frequency table for fluidity, bleeding and compressive strength.

Low or Unreliable Grout Results?

Cause Effect
Too much water added per bag Low strength, high bleed, low efflux time
Insufficient mixing time or a poor mixer Lumps, variable strength, poor flow
Grout sampled from a standing bucket Unrepresentative results
Tamping a flowable grout Segregation in the cube
Plastic moulds with expansive grout Low or erratic strength
Moving cubes before they set Cracked, damaged cubes
Cold overnight curing Under-reported strength
Testing on the trowelled face Lower strength, uneven loading

Remember...

  • Read the product data sheet and follow the stated water range, never the "add water until it flows" approach
  • Use a suitable high-shear or paddle mixer for the mixing time stated
  • Measure water by volume or mass for every bag
  • Run fluidity and density checks before grouting starts
  • Make cubes at the point of placement
  • Protect cubes from heat, cold and disturbance
  • Keep grouting records (duct or anchor ID, volume injected, vents closed, pressures) alongside the test results
  • Where grout transfers load before an operation (for example a ground anchor bond zone or a bearing), obtain the required strength evidence and release before stressing or loading. Bonded PT tendon ducts are normally grouted after stressing; do not confuse duct grout with concrete or anchorage grout needed before stressing.

Managing Grout Results in a LIMS

A LIMS ties each grout cube to its batch: the flow cone or spread, the temperature, when the cubes were moulded and how they were cured, and the strength at each age. Grout is not part of our worked example, but specimen labels, curing records and review work the same way as for concrete cylinders: see Concrete Testing in a LIMS. Whatever system you use, verify the configured method, calculation rules and report wording against the laboratory’s controlled procedure; software output does not itself establish standards compliance or authorise construction work.

Interpreting Results Together

Passing cubes show specimen strength under the stated test conditions. They do not prove a duct or baseplate is completely filled. Review flow and bleed results alongside injected volumes, vents, pressure records, leaks, placement sequence and any specified inspection. A satisfactory 28-day result also cannot retrospectively authorise loading that occurred before the required early strength was demonstrated.

Frequently Asked Questions

What size are grout cubes in Australia?

Typically 50 mm, 70 mm or 75 mm. AS 1478.2 and T375 / TS 02800.49 cover cubes in the 50–75 mm range. Use the size the specification nominates.

Why test grout in cubes rather than cylinders?

Cubes suit the small volumes and fine materials involved, and manufacturer strength claims are usually stated as cube strengths. Concrete is tested in cylinders.

Can I compare grout cube strength with the concrete strength?

Not directly. Cube strengths are generally higher than cylinder strengths for the same material, and the design will usually specify grout strength separately.

What is efflux time?

The time for a fixed volume of grout to flow out of a standard flow cone. It is a measure of fluidity used for post-tensioning and ground anchor grouts.

Why is bleed a problem in PT ducts?

Bleed water rises to high points in the duct and leaves voids when it evaporates or is absorbed. Unprotected strand in those voids is vulnerable to corrosion.


Sources and Method Scope

This learning guide explains purpose, terminology and interpretation. It is not the full test method. Use the project-adopted standards, amendments, specification and controlled laboratory procedure for exact apparatus, timing, conditioning, calculations and decision rules.